Warning – Pennco 3KW0.60 User Manual
Page 17

17
THERMOSTAT
Install 24 Volt thermostat (not provided) in proper location.
Location of thermostat has effect on boiler system operation.
Follow instructions included with thermostat.
GROUNDING
Permanently ground boiler according to local codes and
latest revision of the National Electrical Code. Run 14
gauge or heavier copper wire from boiler to grounded
connection in service panel or properly driven and
electrically grounded ground rod.
ELECTRIC POWER SUPPLY
Installation must comply with the latest revision of the
National Electrical Code, any other national, state, or local
codes or regulations.
Connect 115 volt electrical supply to L1 and L2 terminals
on limit and two thermostat wires to T and T terminals on
same limit. See wiring diagrams, pages 28 & 29.
Run separate circuit from separate over current protection
device in your electrical service entrance panel. Minimum
15 ampere circuit. Locate shutoff switch at boiler. Turn off
during any maintenance. Solder and tape or securely fasten
connections with wire nuts.
OIL BURNER WIRING
For boilers packaged with oil burners, burners are factory
wired.
ELECTRICAL CONNECTIONS
WARNING
Electrical shock hazard. Turn OFF electrical power sup-
ply at service panel before making electrical connections.
Failure to do so could result in death or serious injury.
!