Installation requirements – Osburn OB01111 User Manual
Page 5

5
INSTALLATION REQUIREMENTS
In Canada the CSA B365 Installation Code for Solid Fuel Burning Appliances and Equipment 
and the CSA C22.1 Canadian National Electrical Code are to be followed in the absence of 
local code requirements. In the USA the ANSI NFPA 70 National Electrical Code and NFPA 
211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances are to be 
followed in the absence of local code requirements. 
In addition to the national installation codes, local building and/or fire officials (or other 
authorities having jurisdiction) should be contacted to determine what restrictions and 
installation requirements might locally apply. 
 
When installed and operated as described in these instructions, the 1100 is intended to be 
used as the following: 
 as a residential freestanding stove with vertical or horizontal connector. 
 in a mobile home*. 
 in an alcove. 
 as a Hearth mount stove for masonry or zero clearance fireplaces. 
 
The 1100 is not intended for installation in a sleeping room. 
 
* The 1100 wood stove is ‘mobile home approved’ only with the pedestal option and with 
optional OA10500 and AC02090. 
 
RESIDENTIAL INSTALLATION INSTRUCTIONS
Choose a location for the unit which meets the minimum clearances to combustibles (see 
Figure 1.3). For other than masonry chimneys determine if the factory built chimney will pass 
between the ceiling joists; if not, choose a new location so that it will, while still maintaining 
the minimum clearances. 
 
Mark the location for the floor protection (if required) as noted in Figure 1.3. 
 
Note: If outside air for combustion is to be used it should be provided for at this time. This 
requires that the Osburn Fresh air intake kit Wood (#OA10500) be installed (refer to the 
installation instructions which are provided in the fresh air intake kit). Install the unit. 
