Vcm, vcm-x & vcb-x controllers – Orion System OE392-10 System Manager TS User Manual
Page 48

Zone
Zone
VCM, VCM-X & VCB-X Controllers
SMTS Technical Guide
48
VCB-X Controllers
VCB-X Miscellaneous & Relays Setpoints
Outdoor Sensor Calibration Offset
If the Outdoor Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Enter a positive Sensor Calibration value to raise the
Outdoor Air Temperature Sensor reading and a negative value to lower
the Sensor reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF /
-55.5ºC; Default = 0ºF / 0ºC.
Return Sensor Calibration Offset
If the Return Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset reading to adjust the Sensor’s Sensi-
tivity. Enter a positive Sensor Calibration value to raise the Return Air
Temperature Sensor reading and a negative value to lower the Sensor
reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC;
Default = 0ºF / 0ºC.
Coil Temperature Calibration Offset
If the Coil Temperature Sensor is reading incorrectly, you can use this
option to enter an offset reading to adjust the Sensor’s Sensitivity. Enter
a positive Sensor Calibration value to raise the Coil Temperature Sensor
reading and a negative value to lower the Sensor reading. High limit
= 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC; Default = 0ºF / 0ºC.
Relays Setpoints
Touch the
< Relays>
button to access the Outputs Setpoints
Screens. Touch the radio button next to the desired relay
selection. Choose one relay output from each screen for
Relays 2 through 23 depending on whether you have the
EM1 Module and/or 12 Relay Module installed and confi gured. See
Table 7 on the next page for Relay Defi nitions.
NOTE:
Relay #1 is not confi gurable as it is reserved for the
Supply Air Fan.
Not Used
Digital Compressor
Cooling Stage
Heating Stage
Condenser Fan
Heat Pump Compressor
Heat Pump Reversing Valve
Heat Pump Aux Heat
Heat Pump Emergency Heat
Mod Heat Enable
Mod Cool Enable
Morning Warm Up
Reheat
Preheat
Low Ambient
Exhaust Fan
Economizer
Heat Wheel
Occupied Mode
Override Mode
Alarm Indicator
Relays