Water source heat pump module, Sequence of operation, Technical guide – Orion System Water Source Heat Pump Module User Manual
Page 11: General, Water source heat pump module setpoints

Technical Guide
Water Source Heat Pump Module
11
Sequence of Operation
Table 2: Water Source Heat Pump Module Inputs &
Outputs
General
The following inputs and outputs are available on the Water Source Heat
Pump Module. See Table 2 below to reference the Input/Output Map.
Binary Inputs
1
Circuit A, 1
st
Compressor Enable (BIN 1)
2
Circuit A, 2
nd
Compressor Enable (BIN 2)
3
Circuit B, 1
st
Compressor Enable (BIN 3)
4
Circuit B, 2
nd
Compressor Enable (BIN 4)
5
Cool Enable (BIN 5)
6
Water Proof of Flow (BIN 6)
Analog Inputs
1
Suction Pressure Circuit A (Pres 1)
2
Not Used
3
Suction Pressure Circuit B (Pres 3)
4
Not Used
5
Leaving Water Temperature (T1)
Analog Outputs (1-5 VDC)
1
Circuit A - Digital Compressor A1 (AOUT1)
2
Circuit B - Digital Compressor B1 (AOUT2)
NOTE: Analog Outputs are not used on Stand Alone
Application
Relay Outputs (24 VAC)
1
Circuit A, 1
st
Compressor Enable Output (RLY1)
2
Circuit A, 2
nd
Compressor Enable Output (RLY2)
3
Circuit B, 1
st
Compressor Enable Output (RLY3)
4
Circuit B, 2
nd
Compressor Enable Output (RLY4)
5
Alarm Output (RLY5)
Table 3: Factory-Set Default Setpoints - Water Only
Default Setpoints
Description
Setpoint
UNSAFE SUCTION
40 PSIG
LOW SUCTION HEAT MODE
100 PSIG
LOW SUCTION COOL MODE
100 PSIG
LOW LEAVING WATER TEMP
37ºF
Water Source Heat Pump Module
Setpoints
The Water Source Heat Pump Module setpoints are preset at AAON
and are based on the unit’s design and type of coolant being used in the
water loop. See Tables 3 & 4 for default settings.
NOTE: These are default settings only. The setpoints may be
different based on the unit’s design and type of coolant
being used. For fi eld adjustment of these setpoints, you
must contact the AAON factory.
Glycol Default Setpoints
Description
20% Glycol 40% Glycol
UNSAFE SUCTION
40 PSIG
40 PSIG
LOW SUCTION HEAT MODE
77 PSIG
45 PSIG
LOW SUCTION COOL MODE
85 PSIG
85 PSIG
LOW LEAVING WATER TEMP
23ºF
0ºF
Table 4: Factory-Set Default Setpoints - Glycol
Revised 12/28/11