Wshp-x module, Main screens map and wshp screens, Technical guide – Orion System Water Source Heat Pump X Module User Manual

Page 21: 21 main screens map, Wshp screens

background image

Technical Guide

WSHP-X Module

21

Main Screens Map

Refer to the following map when navigating through the LCD Main
Screens. The fi rst screen is the address screen. To scroll through the rest
of the screens, press the

button.

WSHP

AAON

ALARMS

STATUS

SYSTEM A

STATUS

SYSTEM B

SETPOINT

ADDRESS

#

Press to scroll through ALARMS Screens.

Press to scroll through STATUS SYSTEM A Screens.

Press to scroll through SETPOINT Screens.

Press to go to STATUS SYSTEM A Screens.

Press to go to STATUS SYSTEM B Screens.

Press to go to SETPOINT Screens.

Press to go to ALARM Screens.

Press to scroll through WSHP Screens.

Press to scroll through STATUS SYSTEM B Screens.

Main Screens Map and WSHP Screens

WSHP Screens

Refer to the following map when navigating through the Main Screens.
From the WSHP AAON Screen, press

to scroll through

the screens.

WSHP

AAON

S/A or

COMM MODE or

COM T/O ERROR

SOFTWARE

1053v100

H20 CNFG

SINGLE or DUAL

CURRENT SOFTWARE VERSION

In Stand-Alone Mode, the screen will only display S/A MODE.

In Communications Mode, the screen will display COMM MODE and the
items below will scroll through the screen:

1. Number of good packets being received. This will roll over after 9999.
Example: +XXXX

2. Number of checksum errors. This will stop at 9999. Example: C-XXXX

3. Number of packet length errors. This will stop at 9999 until power is
cycled. Example: P-XXXX

WATER CIRCUIT CONFIGURATION

SINGLE (Typical for AAON Coil) or DUAL (Typical for AAON Tulsa)

REV VALV

OFF=COOL or

OFF=HEAT

REVERSING VALVE CONFIGURATION

OFF=COOL (No signal on reversing valve input equals cool mode)

OFF=HEAT (No signal on reversing valve input equals heat mode)

ADDRESS

#