Wshp-x module, Main screens map and wshp screens, Technical guide – Orion System Water Source Heat Pump X Module User Manual
Page 21: 21 main screens map, Wshp screens
Technical Guide
WSHP-X Module
21
Main Screens Map
Refer to the following map when navigating through the LCD Main
Screens. The fi rst screen is the address screen. To scroll through the rest
of the screens, press the
button.
WSHP
AAON
ALARMS
STATUS
SYSTEM A
STATUS
SYSTEM B
SETPOINT
ADDRESS
#
Press to scroll through ALARMS Screens.
Press to scroll through STATUS SYSTEM A Screens.
Press to scroll through SETPOINT Screens.
Press to go to STATUS SYSTEM A Screens.
Press to go to STATUS SYSTEM B Screens.
Press to go to SETPOINT Screens.
Press to go to ALARM Screens.
Press to scroll through WSHP Screens.
Press to scroll through STATUS SYSTEM B Screens.
Main Screens Map and WSHP Screens
WSHP Screens
Refer to the following map when navigating through the Main Screens.
From the WSHP AAON Screen, press
the screens.
WSHP
AAON
S/A or
COMM MODE or
COM T/O ERROR
SOFTWARE
1053v100
H20 CNFG
SINGLE or DUAL
CURRENT SOFTWARE VERSION
In Stand-Alone Mode, the screen will only display S/A MODE.
In Communications Mode, the screen will display COMM MODE and the
items below will scroll through the screen:
1. Number of good packets being received. This will roll over after 9999.
Example: +XXXX
2. Number of checksum errors. This will stop at 9999. Example: C-XXXX
3. Number of packet length errors. This will stop at 9999 until power is
cycled. Example: P-XXXX
WATER CIRCUIT CONFIGURATION
SINGLE (Typical for AAON Coil) or DUAL (Typical for AAON Tulsa)
REV VALV
OFF=COOL or
OFF=HEAT
REVERSING VALVE CONFIGURATION
OFF=COOL (No signal on reversing valve input equals cool mode)
OFF=HEAT (No signal on reversing valve input equals heat mode)
ADDRESS
#