One condenser head pressure module, Technical guide 8 – Orion System One Condenser Head Pressure Module User Manual
Page 8

One Condenser Head Pressure Module
Technical Guide
8
E-BUS Controller to One Condenser Head Pressure Module Wiring
VCM-X Modular E-BUS or VCM-X WSHP
E-BUS Controller to One Condenser
Head Pressure Module Wiring
Up to (2) One Condenser Head Pressure Modules can be daisy-chained
together and connected to the E-BUS Controller using a modular HSSC
cable. The One Condenser Head Pressure Module requires a 24 VAC
power connection with an appropriate VA rating. See Figure 4 below
for wiring.
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.
NOTE: Contact Factory for the correct HSSC cable length for
your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.
Figure 4: VCM-X E-BUS Controller to Two Condenser Head Pressure Module Wiring Diagram
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
Head Pressure Transducers
0 - 667 PSI
(One Per Refrigerant Circuit)
OE370-23-HP1C
One Condenser Head Pressure Module
OPTIONS Dip Switch Setting Not
Required When Connected To
VCM-X Modular E-BUS or VCM-X
WSHP E-BUS Controller
+5V
SIG 2
GND
OP
T
IO
N
S
ALARM
ANALOG
STAT
+5V
COMM
GND
SIG 4
GND
R1
R2
GND
RELAYS
SIG 3
+5V
GND
+5V
SIG 1
R3
R4
Rc
AO1
AO2
PWM1-
PWM1+
PWM2-
PWM2+
PWR
COM
+
Condenser
Signal A
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
HSSC Cable
24 VAC Transformer
3 VA Minimum
Line Voltage
24 V
A
C
GND
WARNING!! Observe
Polarity! All boards must be
wired with GND-to-GND and
24 VAC-to-24 VAC. Failure to
observe polarity could result in
damage to the boards.
CONDENSER A ENABLE
R1
HVAC UNIT CONNECTION
NOTE:
NORMALLY OPEN AND
RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD
ALL RELAY OUTPUTS
ARE
COMM
HSSC Cable
Connect To VCM-X E-BUS
Controller or VCM-X WSHP E-BUS Controller
Set ADDRESS Dip Switch 1
to ON for Water Cooled or to
OFF for Air Cooled. Currently
showing OFF for Air Cooled.
Set ADDRESS Dip Switch 2
to OFF on all communicating
applications unless it is
intended to be the Second
Head Pressure Module on a
system. If set to ON, it will
not communicate. Currently
showing OFF.
Set ADDRESS Dip Switch 4
to OFF to make reversing
valve "ON to Heat / OFF to
Cool” Set to ON to make
reversing valve “ON to Cool /
OFF to Heat. Currently
showing OFF.
ADDRESS
BIN 1
BIN 2
BIN 3
COM
LED BLINK CODES
LED NAME
STAT
BLINKS QTY. OF SENSORS INSTALLED
LED NAME
ALARM
NO PROBLEMS
0
NO SENSORS DETECTED
1
HIGH HEAD PRESSURE DETECTED
2
LOW HEAD PRESSURE DETECTED
3
WattMaster Label
#LB102057-A
Rev.: 1J
E-BUS
Connector
E-BUS
Connector
+5V
SIG 1
GND
+5V
SIG 2
GND
+5V
SIG 3
GND
+5V
SIG 4
GND
+24
VA
C
GND
HEAD
PRESSURE
TRANSDUCER #1/
HEAD
PRESSURE
TRANSDUCER #2
HEAD
PRESSURE
TRANSDUCER #3
HEAD
PRESSURE
TRANSDUCER #4
PWM2+
One Condenser Head Pressure Module
1C
Orion No.:OE370-23-HP
AAON No.:
R74860
AO1
AO2
GND
COND. SIGNAL
NOT USED
PWM1-
PWM1+
PWM2-
COND. FAN
NOT USED
COND. FAN
NOT USED
GND
RELA
Y
CONT
ACT
RA
TING IS 1
AMP
MAX @ 24 V
AC
COND. ENABLE
NOT USED
NOT USED
R1
R2
R3
R4
RC
RELAY COMMON
BIN 1
BIN 2
BIN 3
COM
NOT USED
COMMON
COND. ENABLE INPUT
REV. VLV. INPUT ENABLE
A1
A2
A3
A4
REV. VLV. ENABLE
www.aaon.com
R2
REVERSING VALVE A ENABLE
+24 Volts
Duty Cycle
YELLOW
BLUE +24 OUT
Condenser Fan
ECM Motor