Technical Guide

One Condenser Head Pressure Module

23

Appendix for Version 1.06 and Earlier

ADDRESS Dip Switch 1 & 2 Settings

Switch 1

Switch 2

Default SP

Description of Default Head Pressure Setpoint

OFF

OFF

340

Air Cooled Condenser using R410-A Refrigerant

OFF

ON

200

Air Cooled Condenser using R22 Refrigerant

ON

OFF

235

Water Cooled Condenser using R410-A Refrigerant

ON

ON

145

Water Cooled Condenser using R22 Refrigerant

Switch 1 determines Air or Water Cooled Condenser

Switch 2 determines R410-A or R22 refrigerant

NOTE: R22 refrigerant can only be used with the One Condenser Head Pressure Module versions 1.03 to 1.06.

You must cycle power after setting Dip Switch values.

Table 10: ADDRESS Dip Switch Refrigerant and Condenser Type Settings for Stand-Alone Operation