Environmental Requirements

The Full Digital Module needs to be installed in an environment which
can maintain a temperature range between -30°F and 150°F and not
exceed 90% RH levels (Non-Condensing).

Mounting

The Full Digital Module is housed in a plastic enclosure. It is designed
to be mounted by using the 3 mounting holes in the enclosure base. It is
important to mount the module in a location that is free from extreme high
or low temperatures, moisture, dust, and dirt. Be careful not to damage
the electronic components when mounting the module.

See Figure 2 for Module dimensions (dimensions are in inches).

Power Supply and Communications

The Full Digital Module is connected to the E-BUS Distribution Mod-
ule with a modular HSSC cable to provide communications from the
VCM-X Modular Controller. The E-BUS Distribution Module uses
WattMaster Control’s standard I

2

C modular cable to connect with the

VCM-X Modular Controller, VCM-X Expansion Module, or 12-Relay
Expansion Module.

The Full Digital Module can also be directly connected to the VCM-X
Modular E-BUS Controller, bypassing the use of the E-BUS Distribu-
tion Module.

The Full Digital Module requires a 24 VAC power supply with an ap-
propriate VA rating.

WARNING: Observe polarity! All boards must be wired

GND-to-GND and 24 VAC-to-VAC. Failure to

observe polarity could result in damage to the

boards.

Installation and Wiring

Figure 2: Full Digital Module Dimensions