Wiring, Modgas-x field technical guide – Orion System MODGAS-X User Manual
Page 5

MODGAS-X Field Technical Guide
WIRING
5
Single Modulating Valve No Staging - Stand-Alone Wiring
Figure 2: Single Modulating Valve No Staging Stand-Alone Wiring Diagram
MODGAS-X CONTROLLER
(OE377-26-00058)
Fan Enable And
Modulating Heat Enable
Low Speed Fan
See
For
Settings.
Only One Supply Air Temperature Sensor
Can Be Used Per Application.
Table 8, Page 24
SAT OPTIONS Jumper
Connect SAT and
Input to
Board’s
Input If
Applicable.
See
.
GND
Reheat
SAT
Table 7,
Page 24
24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA
2 Gas Valves
= 33 VA
Single Modulating Valve No Staging -
Stand-Alone Wiring
This confi guration operates as Stand-Alone (Figure 2, below) or
communicating with an AAON Unit Controller (Figure 3, page 6).
This confi guration
can use either the MAXITROL
®
0-20 volt valve(s)
or the MAXITROL
®
EXA STAR 0-10 volt stepper valve(s)—confi g-
ured at the factory.
See Appendix C, page 26 for depiction.
If using a MHGRV-X Controller along with the MODGAS-X
Controller in Stand-Alone, the SAT Sensor always connects to the
MODGAS-X Controller.
WARNING: Do Not Connect Power To VOUT/Ground
Terminal
Block!