beautypg.com

Appendix e - sa controller lon parameters, Pt-link-lon, Technical guide – Orion System PT-Link-LON User Manual

Page 28: Pt-link interface 28

background image

PT-Link-LON

®

Technical Guide

PT-Link Interface

28

Appendix E - SA Controller LON Parameters

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Dewpoint

Setpoint

DptSt

Analog

Input

If the outdoor

dewpoint rises above

this setpoint, the

unit will activate the

Dehumidifi cation

Demand.

35

80

Occupied/

Mode

Enable

Cooling

Setpoint

OcpClSt

Analog

Input

If the control

temperature rises one

degree above this

setpoint, the control

will activate the cool-

ing demand. If the

control temperature

is the Supply Air Sen-

sor, then the cooling

demand is always

active.

0

99

Occupied/

Mode

Enable

Heating

Setpoint

OcpHtSt

Analog

Input

If the control

temperature drops

one degree below

this setpoint,

the control will

activate the heating

demand. If the

control temperature

is the Supply Air

Sensor, then there is

no heating demand.

99

Schedule

Force

SchdFrc

Analog

Input

0 = Auto/

Unoccupied Mode

1 = Forced On

2 = Forced Off

0

2

Space

Sensor

Offset

SpcTpOst

Analog

Input

If the Space

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

SAT/Reset

Source

Cooling

Setpoint

SaClSt

Analog

Input

Supply Air setpoint

or Reset Source

target temperature in

Cooling Mode.

40

80

SAT/Reset

Source

Heating

Setpoint

SaHtSt

Analog

Input

Supply Air setpoint

or Reset Source

target temperature in

Heating Mode.

40

200

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Supply Air

Sensor Offset

SaTpOst

Analog

Input

If the Supply Air

Temperature Sensor

is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Warm Up

Setpoint

WmupSt

Analog

Input

In a VAV

application, upon

entering the

occupied mode, the

Warm-up Demand

will be activated

if the return air

temperature falls

one degree below

this setpoint.

50

90

Coil

Temperature

Setpoint

CoilTpSt

Analog

Input

This is the coil

suction temperature

target during

dehumidifi cation

mode. Produces

dewpoint in the

supply air

approximately 10°F

above this setpoint.

35

70

Indoor

Humidity

Setpoint

InRhSt

Analog

Input

If the indoor

humidity rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

0

100

Unoccupied

Cooling

Offset

UnClOst

Analog

Input

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied Cool-

ing Setpoint out by

a user adjustable

amount. If you do

not want Cooling to

operate during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30