Gbd-x controller, Ss1029 – Orion System GBD-X Controller User Manual
Page 3

Filename: GBD-XControllersInfo-SS1029-1B.doc
Page 1 of 2
8500 NW River Park Drive
• Parkville, Mo. • 64152
Phone (816) 505-1100 E-mail: [email protected] Fax (816) 505-1101
GBD-X Controller
SS1029
DESCRIPTION:
The GBD-X Controller has the ability to monitor up to 12 temperature
sensors and broadcast the average of those sensors to a VCM or
VCM-X controller. It also includes the ability to read CO
2
sensors and
either average or find the highest reading to be broadcast to the same
controllers. It also provides a 0-10 VDC proportional reset voltage on
Analog Output #1 based on the level of CO
2
as it rises from an
adjustable minimum setting to an adjustable maximum level.
Analog Output #2 provides a 10.0 VDC signal whenever the CO
2
is
above the minimum setpoint.
Relay #1 is activated whenever the CO
2
rises above the minimum
setting and de-activates when it falls 5 PPM below the setpoint.
Relay #2 is activated whenever the CO
2
rises above the maximum
setting and de-activates when it falls 5 PPM below the setpoint.
LIMITATIONS:
When using the GBD-X controller you must have the following
minimum equipment installed on your controls system:
Single Loop System requires either a CommLink or a MiniLink to allow
broadcasting to and from the GBD-X controller.
Multiple Loop Systems require both a CommLink and a MiniLink to
allow broadcasting to and from the GBD-X controller.
Only 6 sensors can be connected to a single GBD-X controller. If more
than 6 sensors are needed then a second GBD-X controller board for
sensors 7 to 12, is required. The global analog broadcast channels are
user selectable.
Celsius temperatures are not supported.
Only the VCM and VCM-X Controllers can read the CO
2
for IAQ
operations.
Any VCM or VCM-X on a loop can have broadcast devices sending
it data since the global receive channel is fixed at Global Analog
#13 for temperature (if no space sensor installed) and #14 for CO
2
(if no sensor is installed).