Technical Guide

E-BUS Distribution Module

7

Installation and Wiring

E-BUS Terminal Blocks TB1 and TB2

Wiring

The E-BUS Terminal Blocks TB1 and TB2 provide an alternate method
of connecting the E-BUS Distribution Module to the other modules. This
method is used when it is necessary to pull the wire through conduit or
to extend the length.

WARNING: Power down the E-BUS Distribution Module

and E-BUS Module(s) before splicing the

HSSC

cable.

Figure 5: E-BUS Distribution Terminal Block Wiring

After removing the connector from the E-BUS Distribution end of the
HSSC cable, wire or splice to the terminal blocks as follows:

NOTE: When extending the HSSC cable, do not exceed 200

feet without factory approval.

+ COMM

Black wire

RS-485 (+) communications

SHLD

Green wire

Shield or common internally tied

to

GND

- COMM

White wire

RS-485 (-) communications

GND

Not

used

+ VDC

Not used

Unregulated +DC voltage for

powering

certain

sensors