E-bus adapter board, Technical guide 6, Line voltage – Orion System OE365-15-EBA User Manual
Page 6
E-BUS Adapter Board
Technical Guide
6
E-BUS Modules and/or Sensors to VCB-X Controller Wiring
Figure 4: Multiple E-BUS Sensors Wiring to VCB-X Controller Using the E-BUS Adapter
Connecting Multiple E-BUS Modules
and/or Sensors to the VCB-X
Controller
If using multiple E-BUS Sensors or Modules, the E-BUS Adapter
Board can be used when there are not enough available E-BUS ports
on the Unit Controller.
Up to (3) E-BUS Modules or Sensors can be connected to the E-BUS
Adapter Board(s) MODBUS E-BUS ports. The VCB-X Control-
ler connects to the fourth MODBUS E-BUS port on the E-BUS
Adapter Board.
See Figure 4 for wiring details when connecting multiple E-BUS
modules and/or sensors to the VCB-X Controller.
OE265-15-A Horizontal
Temperature
& Humidity Sensor
EBC E-BUS Cable with
Jack Connection
NOTE: Connect both
Sensors to the E-BUS
Adapter’s Modular
E-BUS Ports Using The
Provided EBC E-BUS
Cables.
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
AO2
AO3
TR1
= SC
= DIGITAL CO
TRIAC OUTPUT
LED N
M
NORMAL
SAT FAIL
OAT FAIL
SPC FAIL
MECH COOL FAIL
MECH HEAT FAIL
FAN PROOF FAIL
DIRTY FILTER
EMERGENCY SHUTDOWN
LOW SAT
1
HIGH SAT
2
CONT. TEMP COOL FAIL
3
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
OUTPUT FORCE ACTIVE
0
6
WattMaster Label
#LB102093-01-A
Rev.: 1C
E-BUS
EXPANSION
E-BUS
EXPANSION
24 VAC
INPUT
=
37X04
1.2
1.6
4 3 2 1
3M
OE256-07 Duct Mounted
E-BUS CO Sensor
2
37X04
1.2
1.6
4 3 2 1
3M
EBC E-BUS Cable
with Jack
Connection
OE365-15-EBA
E-BUS Adapter Board
OE335-23-VCBX
VCB-X Controller
NOTE: Connect
the VCB-X
Controller To The
E-BUS Adapter’s
Modular E-BUS
Port.
24VAC
GND
Line
Voltage
WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA