Online power, Danger – OnLine Power Iso-Care User Manual
Page 14
OnLine Power
6002-033
Rev
C
3-1
SECTION 3 - INSTALLATION
The following instructions cover general requirements for changing the input voltage configuration and for installing the
primary input power and secondary output power circuits for the Iso-Care and NRT transformers.
DANGER!!
VERIFY THAT INCOMING HIGH VOLTAGE CIRCUITS ARE DE-ENERGIZED BEFORE
CHANGING VOLTAGE CONFIGURATION, INSTALLING CABLES OR MAKING ANY
CONNECTIONS.
3-1
INPUT AND OUTPUT POWER CIRCUITS
The customer-furnished primary input power circuit provides power from the building source to the Iso-Care or NRT. The
customer-furnished secondary output power circuit provides power from the Iso-Care or NRT to the customer’s equipment.
The Iso-Care and NRT have one(1) conduit cutout on the left and right side of the unit’s frame to accommodate the input and
output power cables. Refer to Illustration 2-1 or 2-2.
The front and rear panels should be removed by unbolting six fasteners located on sides of the front and rear panels.
If cables are crossed or wires are likely to touch, insulating sleeves or their equivalent must be used to prevent wires from
touching.
DANGER!!
POTENTIAL ELECTRICAL HAZARDS TO HUMAN LIFE EXIST WITHIN THIS EQUIPMENT
WHEN ENERGIZED. DISCONNECT INPUT POWER TO UNIT BEFORE OPENING
ENCLOSURE OR TOUCHING INTERNAL PARTS.
CAUTION
Input power connection and required branch circuit breaker should be installed by a licensed
electrical contractor in accordance with local codes. Primary and secondary power circuit
conductors must not touch each other. If conductors touch, use insulating sleeves.