SECTION 2 - PREINSTALLATION
2-1
LOCATION CONSIDERATIONS
Provide an operating environment which meets the following conditions:
Ambient Temperature
0° to 40° C (32° to 104° F)
Relative Humidity
10 to 95% Non-condensation
POSITIONING.
Position the unit so there is easy access to the front of the regulator. Allow at least 3 inches to
each side and rear of the units. All units can be serviced from the front as long as the 3 inches are maintained on
each side to remove the top cover. This unit is air cooled by convection. Do not block the air flow from the
bottom, sides, or front of the unit.
TABLE 2-1
CONSTANT POWER 6 SITE PLANNING SPECIFICATIONS
NOMINAL INPUT VOLTAGE
120
208-220-240
480
INPUT VOLTAGE RANGE
88.8-132
153.9-229, 163-242, 177.6-264
355-528
MAXIMUM INPUT VOLTAGE
132
229, 242, 264
528
FREQUENCY
60 HZ +/-5%
60 HZ +/-5%
60 HZ +/-5%
AMBIENT TEMPERATURE
°F (°C)
80 (26.7)
80 (26.7)
80 (26.7)
kVA
SIZE
INPUT
VOLTAGE
NOMINAL
INPUT RATED
CURRENT
HEAT
REJECTION
BTU/hr
WEIGHT lbs (kg)
SIZE H x W x D in. (cm)
WITHOUT PACKAGING
3
120
25
408
115 (52)
19.5 X 14.5 X 25.5
(50 X 37 X 65)
208-220-240
14.4-13.6-12.5
480
6.25
5
120
41.67
680
140 (64)
208-220-240
24 -27.7-20.8
480
10.42
8
120
66.67
1080
210 (95)
208-220-240
38.5-36.4-33.3
480
16.7
10
208-220-240
48-45.5-41.7
1360
230 (105)
480
20.83
15
208-220-240
72.1-68.2-62.5
2040
280 (127)
480
31.25