Reported Problem
Possible Solutions
Network communications are 
disrupted when the device is 
connected.
• The RS485 network cable connections are polarity
sensitive and must be connected the same way on 
every device (i.e. + to + and - to -). (See section 1.4.1 of 
this manual for details.)
• Is the transmit LED flashing? The transmit LED will
only flash when the device is responding to a poll. 
A unique address is required for each device on the 
network. Duplicate addresses will cause some or all 
of the devices on the network to quit working. (See 
section 1.6.1 of this manual for details.)
• A unique IP address is required for each device on
TCP/IP networks. Duplicate addresses will cause 
multiple devices to respond to the same poll. This will 
cause some or all of the devices on the network to quit 
working. (See section 1.6.2 of this manual for details.) 
Network communications are 
disrupted when the device is 
connected (cont.).
• Shield drain connections should be daisy
•
chained in the same manner as the
•
signal cables for RS485. The shield drain
•
wire should be left unterminated at the
•
end of the cable and connected to earth
•
only at the network master controller.
•
Shield wires must not be connected to the
•
RS485 connector on the D-100.