ONICON D-100 BACnet User Manual
Page 23

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100 Display Module BACnet Installation and Operation Guide 05/14 - 0635-6 / 18341 
Page 23
3.1 TROUBLESHOOTING
Reported Problem
Possible Solutions
Device will not communicate 
with the network controller.
• Is the receive LED flashing on the network board? This
LED will flash whenever there is traffic on the network. If 
the LED is not flashing, look for an open network cable.
• Is the transmit LED flashing? The transmit LED will only
flash when the device is responding to a poll. A unique 
address is required for each device on the network. 
Duplicate addresses will cause some or all of the devices 
on the network to quit working. (See section 1.6.1 of this 
manual for details.)
• The RS485 network cable connections are polarity
sensitive and must be connected the same way on every 
device (i.e. + to + and - to -). (See section 1.4.1 of this 
manual for details.)
• The Baud rate setting must match the network Baud rate.
(See section 1.5.1 of this manual for details.)
• Shield drain connections should be daisy chained in the
same manner as the signal cables for RS485. The shield 
drain wire should be left unterminated at the end of the 
cable and connected to earth only at the network master 
controller. Shield wires must not be connected to the 
RS485 connector on the D-100.
• The maximum number of devices allowed on an RS485
network segment without a repeater is 32. Adding more 
than 32 devices to a single segment may reduce the 
transceiver output voltage to a level that is too low to be 
distinguished from background noise on the cable.
Device will not communicate 
with the network controller. 
(cont.)
• RS485 cable impedance should be matched to a
termination resistor at the end of the cable. ONICON 
boards have a jumper selectable 120 ohm resistor for 
termination. This resistor should only be used if the 
display is the last device on the network cable. (See 
section 1.5.2 of this manual for details.)
• A unique IP address is required for each device on TCP/
IP networks. Duplicate addresses will cause multiple 
devices to respond to the same poll. This will cause some 
or all of the devices on the network to quit working. (See 
section 1.6.2 of this manual for details.) 
• Managed IP networks may require that a gateway IP
address be programmed into the ONICON TCP/IP device. 
(See section 1.6.3 of this manual for details.)
SECTION 3.0: NETWORK TROUBLESHOOTING TIPS
