ONICON D-100 BACnet User Manual
Page 13

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100 Display Module BACnet Installation and Operation Guide 05/14 - 0635-6 / 18341 
Page 13
STEP
ACTION
REACTION
COMMENT
0
Obtain MAC address & device 
instance number from the 
network administrator. 
None.
The MAC address is a three digit 
number from 001 – 254. The 
device instance number can be 
anything from 0 – 4,194,303.
1
With the display running, open 
the front panel, locate and 
momentarily press the
pushbutton switch DEV ADD / 
PROG ENAB.
None.
DEV ADD / PROG ENAB is 
located in the lower left corner 
of the D-100 processor board 
next to the DB9 connector (See 
appendix page A-1).
2
Momentarily press the 
PROGRAM pushbutton on the 
front panel of the display. If 
this is not done, the display 
will revert to the RUN mode 
after 5 minutes.
The D-100 will change to the 
PROGRAM mode. The top line of 
the LCD will indicate PPPPPPPP.
The second line will read DEVICE 
ID and the first digit of the 3 digit 
MAC address will be blinking.
The PROGRAM pushbutton is 
the rightmost pushbutton on the 
front panel user interface.
3
Successively press the SCROLL 
pushbutton to increment the 
number to the desired value 
from 0 – 9.
The blinking number increments 
by one each time you press the 
SCROLL pushbutton. 
The SCROLL pushbutton is the 
leftmost pushbutton on the front 
panel user interface.
4
Momentarily press the RESET 
pushbutton once.
The second digit will now be 
blinking.
The RESET pushbutton is the 
center pushbutton on the front 
panel user interface.
5
Successively press the SCROLL 
pushbutton to increment the 
number to the desired value 
from 0 – 9.
The blinking number increments 
by one each time you press the 
SCROLL pushbutton.
The SCROLL pushbutton is the 
leftmost pushbutton on the front 
panel user interface.
6
Momentarily press the RESET 
pushbutton once.
The third digit will now be 
blinking.
The RESET pushbutton is the 
center pushbutton on the front 
panel user interface.
7
Successively press the SCROLL 
pushbutton to increment the 
number to the desired value 
from 0 – 9.
The blinking number increments 
by one each time you press the 
SCROLL pushbutton.
The SCROLL pushbutton is the 
leftmost pushbutton on the front 
panel user interface.
8
Once the correct address is 
displayed, momentarily press 
the PROGRAM pushbutton.
The INSTNCE page is now 
displayed with the first digit 
of the device instance number 
blinking.
The PROGRAM pushbutton is 
the rightmost pushbutton on the 
front panel user interface.
9
Use the SCROLL pushbutton 
and RESET pushbutton as 
described above to enter the 
new device instance number.
Each digit will increment and the 
RESET pushbutton will advance 
the blinking cursor to the next 
digit.
The SCROLL pushbutton is 
the leftmost pushbutton on the 
front panel user interface. The 
RESET pushbutton is the center 
pushbutton on the front panel 
user interface.
10
Once the correct address is 
displayed, momentarily press 
the PROGRAM pushbutton.
The FRONT PANEL RESET page 
appears.
It is not necessary to change 
anything on this page.
11
Momentarily press the 
PROGRAM pushbutton.
The SAVE CHANGES page 
appears.
The new addresses must be 
saved to take effect.
12
Momentarily press the SCROLL 
pushbutton.
The “N” changes to “Y” on the 
SAVE CHANGES page.
The “Y” must be selected in order 
for the new addresses to take effect.
13
Momentarily press the
PROGRAM pushbutton.
The new addresses are saved and the
display will revert to the RUN mode.