Register
Address
Description
Register
Range
Data
Range
Over
Range
Read/Write
Comment
40042
Volume Total Mode 1 - kGal
0 – 65535 0 – 999
Read Only
Low Order
40043
Volume Total Mode 1 - MGal
0 – 65535 0 – 999
Read Only
Middle Order
40044
Volume Total Mode 1 – GGal
0 – 65535 0 – 65534
65535
Read Only
High Order
40045
Volume Total Mode 2 – kGal
0 – 65535 0 – 999
Read Only
Low Order
40046
Volume Total Mode 2 – MGal
0 – 65535 0 – 999
Read Only
Middle Order
40047
Volume Total Mode 2 – GGal
0 – 65535 0 – 65534
65535
Read Only
High Order
40048
Volume Total Mode 1 – kLiters 0 – 65535 0 – 999
Read Only
Low Order
40049
Volume Total Mode 1
–
MLiters 0 – 65535 0 – 999
Read Only
Middle Order
40050
Volume Total Mode 1 – GLiters 0 – 65535 0 – 65534
65535
Read Only
High Order
40051
Volume Total Mode 2 – kLiters 0 – 65535 0 – 999
Read Only
Low Order
40052
Volume Total Mode 2
–
MLiters 0 – 65535 0 – 999
Read Only
Middle Order
40053
Volume Total Mode 2 – GLiters 0 – 65535 0 – 65534
65535
Read Only
High Order
40054
Volume Total Mode 1 –M³
0 – 65535 0 – 999
Read Only
Low Order
40055
Volume Total Mode 1 – kM³
0 – 65535 0 – 65534
65535
Read Only
High Order
40056
Volume Total Mode 2 –M³
0 – 65535 0 – 999
Read Only
Low Order
40057
Volume Total Mode 2 – kM³
0 – 65535 0 – 65534
65535
Read Only
High Order
40058
Mass Total – kLbs
0 – 65535 0 – 999
Read Only
Mass units are only
available when using
F-2200 Vortex Meter.
40059
Mass Total – MLbs
0 – 65535 0 – 65534
65535
Read Only
40060
Mass Total – Kkgs
0 – 65535 0 – 999
Read Only
40061
Mass Total – Mkgs
0 – 65535 0 – 65534
65535
Read Only
40062
Auxiliary Input Total (Di3)
0 – 65535 0 – 999
Read Only
Low Order
40063
Auxiliary Input Total (x1000)
0 – 65535 0 – 65534
65535
Read Only
High Order
40065
Zero (+) Mode 1 Volume Total
0 – 1
0 – 1
Not
applicable
Read/Write
Write a value of 1 to
registers to reset totals.
Re-write a value of zero
to registers once the
totals reset.
40067
Zero (-) Mode 2 Volume Total
0 – 1
0 – 1
Not
applicable
Read/Write
40068
Zero Auxiliary Input Total (Di3)
0 – 1
0 – 1
Not
applicable
Read/Write