ONICON D-100 Dualnet User Manual
Page 22

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100 Dual Network Interface Installation Guide 07/14 - 1015
Page 22
Register
Address
Description
Register Type
Read/Write
Comment
41047
Volume Total Mode 1 –Gal
Floating point register (1 of 2)
Read Only
41048
Volume Total Mode 1 –Gal
Floating point register (2 of 2)
Read Only
41049
Volume Total Mode 2 –Gal
Floating point register (1 of 2)
Read Only
41050
Volume Total Mode 2 –Gal
Floating point register (2 of 2)
Read Only
41051
Volume Total Mode 1 – Liters
Floating point register (1 of 2)
Read Only
41052
Volume Total Mode 1 – Liters
Floating point register (2 of 2)
Read Only
41053
Volume Total Mode 2 – Liters
Floating point register (1 of 2)
Read Only
41054
Volume Total Mode 2 – Liters
Floating point register (2 of 2)
Read Only
41055
Volume Total Mode 1 – M³
Floating point register (1 of 2)
Read Only
41056
Volume Total Mode 1 – M³
Floating point register (2 of 2)
Read Only
41057
Volume Total Mode 2 – M³
Floating point register (1 of 2)
Read Only
41058
Volume Total Mode 2 – M³
Floating point register (2 of 2)
Read Only
41079
Volume Total Mode 1 – Ft³
Floating point register (1 of 2)
Read Only
41080
Volume Total Mode 1 – Ft³
Floating point register (2 of 2)
Read Only
41081
Volume Total Mode 2 – Ft³
Floating point register (1 of 2)
Read Only
41082
Volume Total Mode 2 – Ft³
Floating point register (2 of 2)
Read Only
41059
Mass Total –Lbs
Floating point register (1 of 2)
Read Only
Mass units are only
available when using
F-2000 Vortex Meter.
41060
Mass Total –Lbs
Floating point register (2 of 2)
Read Only
41061
Mass Total –kg
Floating point register (1 of 2)
Read Only
41062
Mass Total –kg
Floating point register (2 of 2)
Read Only
41063
Auxiliary Input Total (Di3)
Floating point register (1 of 2)
Read Only
41064
Auxiliary Input Total (Di3)
Floating point register (2 of 2)
Read Only
41066
Zero (+) Mode 1 Volume Total
0 – 1
0 – 1
Not
applicable
Read/Write
Write a value of 1 to
registers to reset totals.
Re-write a value of zero
to the register once the
totals reset.
41068
Zero (-) Mode 2 Volume Total
0 – 1
0 – 1
Not
applicable
Read/Write
41069
Zero Auxiliary Input Total (Di3)
0 – 1
0 – 1
Not
applicable
Read/Write
41070
Reserved for future use