ONICON D-100 Dualnet User Manual
Page 20

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100 Dual Network Interface Installation Guide 07/14 - 1015
Page 20
Networking Information
MODBUS RTU
MODBUS TCP
Connection Information
RS485, 2-wire half-duplex
Base 10T, 10Mbps, RJ 45 Connection
Data format / Parity
8 bits, 1 stop bit / None
8 bits, 1 stop bit / None
Flow Control (handshaking)
None
None
Device Address Range
1 - 247
1 - 247
IP Address
Not required
Default address: 192.168.1.24
Termination (selectable)
120 W or none (default none)
None
Biasing
None
None
3.2 MODBUS MEMORY MAP TABLE
Available Engineering Units
Engineering Units
Abbreviation
Volume Rate (Flow)
Gallons per minute
GPM
Gallons per minute x 10
GPM x 10
Gallons per hour
GPH
Million gallons per day
MGD
Liters per second
L/S
Liters per minute
L/M
Liters per hour
L/Hr
Cubic meters per hour
M³/Hr
Cubic meters per hour x 10
M³/Hr x 10
Cubic Feet per second
Ft³/S
Cubic Feet per minute
Ft³/M
Mass Rate (Mass Flow) –
Only available with F-2000 Flow Meter
Pounds per hour
Lb/Hr
Pounds per hour x 10
Lb/Hr x 10
Kilograms per hour
kg/Hr
Kilograms per hour x 10
kg/Hr x 10
Temperature
Degrees Fahrenheit
°F
Degrees Celsius
°C
Generic
None
Engineering Units
Abbreviation
Volume Total
Gallons x 1,000
kGal
Gallons x 1,000,000
MGal
Gallons x 1,000,000,000
GGal
Liters x 1,000
kLiters
Liters x 1,000,000
MLiters
Liters x 1,000,000,000
GLiters
Cubic Meters
M³
Cubic Meters x 1,000
kM³
Cubic Feet
Ft³
Mass Total -
Only available with F-2000 Flow Meter
Pounds x 1,000
kLbs
Pounds x 1,000,000
MLbs
Kilograms x 1,000
Kkg
Kilograms x 1,000,000
Mkg