Register
Address
Description
Register Type
Read/Write
Comment
41009
Volume Rate – GPM
Floating point register (1 of 2)
Read Only
41010
Volume Rate – GPM
Floating point register (2 of 2)
Read Only
41011
Volume Rate – GPH
Floating point register (1 of 2)
Read Only
41012
Volume Rate – GPH
Floating point register (2 of 2)
Read Only
41013
Volume Rate – MGD
Floating point register (1 of 2)
Read Only
41014
Volume Rate – MGD
Floating point register (2 of 2)
Read Only
41015
Volume Rate – L/S
Floating point register (1 of 2)
Read Only
41016
Volume Rate – L/S
Floating point register (2 of 2)
Read Only
41017
Volume Rate – L/M
Floating point register (1 of 2)
Read Only
41018
Volume Rate – L/M
Floating point register (2 of 2)
Read Only
41019
Volume Rate – L/Hr
Floating point register (1 of 2)
Read Only
41020
Volume Rate – L/Hr
Floating point register (2 of 2)
Read Only
41021
Volume Rate – M³/Hr
Floating point register (1 of 2)
Read Only
41022
Volume Rate – M³/Hr
Floating point register (2 of 2)
Read Only
41071
Volume Rate – Ft³/S
Floating point register (1 of 2)
Read Only
41072
Volume Rate – Ft³/S
Floating point register (2 of 2)
Read Only
41073
Volume Rate – Ft³/M
Floating point register (1 of 2)
Read Only
41074
Volume Rate – Ft³/M
Floating point register (2 of 2)
Read Only
41023
Mass Rate – Lb/Hr
Floating point register (1 of 2)
Read Only
Mass units are only
available when using
F-2000 Vortex Meter.
41024
Mass Rate – Lb/Hr
Floating point register (2 of 2)
Read Only
41025
Mass Rate – Kg/Hr
Floating point register (1 of 2)
Read Only
41026
Mass Rate – Kg/Hr
Floating point register (2 of 2)
Read Only
41027
Supply Temperature – °F
Floating point register (1 of 2)
Read Only
41028
Supply Temperature – °F
Floating point register (2 of 2)
Read Only
41029
Return Temperature – °F
Floating point register (1 of 2)
Read Only
41030
Return Temperature – °F
Floating point register (2 of 2)
Read Only
41031
Supply Temperature – °C
Floating point register (1 of 2)
Read Only
41032
Supply Temperature – °C
Floating point register (2 of 2)
Read Only
41033
Return Temperature – °C
Floating point register (1 of 2)
Read Only
41034
Return Temperature – °C
Floating point register (2 of 2)
Read Only
41075
Generic Rate Ai3
Floating point register (1 of 2)
Read Only
There are no engineering
units associated with
these registers.
41076
Generic Rate Ai3
Floating point register (2 of 2)
Read Only
41077
Generic Rate Ai4
Floating point register (1 of 2)
Read Only
41078
Generic Rate Ai4
Floating point register (2 of 2)
Read Only
Register
Address
Description
Register
Range
Data
Range
Over
Range
Read/Write
Comment
41001
Meter Operating Mode
Indicator
1 – 3
Not
applicable
Read Only
1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode
41002
Mode Status Indicator
1 – 2
Not
applicable
Read Only
1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction