System-30 BTU Measurement System MODBUS RTU RS485 04/14 - 0583-1 / 18345

Page 6

1.3 STANDARD FEATURES AND SPECIFICATIONS


Single mode Btu calculations, in either the heating or cooling mode, are totalized and

reported.

Two-pipe dual mode Btu calculations in both the heating mode and the cooling mode are

totalized and reported separately.

Auxiliary pulse input for totalizing pulse outputs from external devices such as water or

gas meters.

GENERAL SPECIFICATIONS

CALIBRATION
Flow sensor and temperature sensors are individually
calibrated, followed by a complete system calibration.
Field commissioning is also available.

ACCURACY
Differential temperature accuracy ±0.15° F over
calibrated

range

Computing non-linearity within ±0.05%
Flow sensor accuracy:
±0.5% OF READING at calibrated velocity
±1% OF READING from 3 to 30 ft/s (10:1 range)
±2% OF READING from 0.4 to 20 ft/s (50:1 range)

TEMPERATURE SENSORS
Solid state sensors are custom calibrated using N.I.S.T.
traceable temperature standards.

PROGRAMMING
Factory programmed for each specific application

MEMORY
Nonvolatile EEPROM memory retains all program
parameters and totalized values in the event of power
loss.

OUTPUT SIGNALS
Isolated solid state dry contacts for mode 1 and mode
2 energy total
Contact rating: 100 mA, 50VDC maximum
Contact duration: 0.5, 1, 2 or 6 sec selectable

NETWORK INTERFACE
MODBUS RTU Protocol
RS485, 2-wire (half duplex)

MODBUS REGISTERS
Total Energy (Btu, ton-hr(s), kw-hr)
Energy Rate (Btu/hr, tons, kw)
Total Flow (gallons, liters, cubic meters)
Flow Rate (gpm, l/s, l/m, m

3

/hr)

Supply Temperature (°F, °C)
Return Temperature (°F, °C)
Mode (Heating-Cooling) Indicator
Aux Total (Count)

BAUD RATE
1200, 2400, 4800, 9600, 19200, 38400, 57600 &
115200 bps

INPUT SIGNALS

One isolated auxiliary pulse input for totalization

(Factory configurable for active pulse, open collector
sinking, open collector sourcing or dry contact pulses)

3 – 24V dc
50Hz maximum frequency
10msec minimum pulse duration

OPTIONAL LOCAL DISPLAY

Alphanumeric backlit LCD displays total energy, total,

flow, energy rate, flow rate, supply temperature and return
temperature

Alpha: 16 characters, 0.2” high
Numeric: 6 digit, 0.4” high

MAINTENANCE

ONICON recommends periodic inspection and recalibration.

No other periodic maintenance is required.

TEMPERATURE RANGE
Liquid temperature range: 32° to 200°F
Ambient temperature range: 40° to 120°F

MECHANICAL
OVERALL DIMENSION:
9.25” L x 5” W x 6.5” H
TEMPERATURE THERMOWELL:
Brass thermowell (½” sweat or ¼” NPT)

ELECTRICAL
This equipment is intended for INSTALLATION
CATEGORY (OVERVOLTAGE CATEGORY) II
applications
INPUT VOLTAGE: 24 V ±10% AC 50/60 Hz or

24

V

±4

DC

INPUT CURRENT: 200 mA maximum

TERMINALS CONNECTIONS: Use 18-22 ga. Copper wire. Do

not exceed 4.5 in-lb (0.5 Nm) of torque when tightening.

WIRING:
CONDUIT: Use PVC jacketed copper cable with a wire Gauge

suitable for the length of run and required maximum current
carrying capacity. The installation must comply with all
local, state and federal codes.

PLENUM AREA: (without conduit) Use plenum rated

copper cable with a wire gauge suitable for the length of
run and required maximum current carrying capacity. The
installation must comply with all local, state and federal
building codes.