4.5 BAUD RATE
Every ONICON Btu meter is individually programmed at the factory with application specific
data provided by the customer during the process of ordering the meter. This normally
includes the Baud rate setting. If the Baud rate was provided, the Btu meter will be configured to
operate at the specified rate. The available Baud rate settings are listed in the table below.
If the Baud rate setting was not provided to ONICON, the Btu meter will be configured to 9600.
The Baud rate setting can be manually changed in the field. The drawing and table below show
the Baud rate dipswitch settings.
Baud Rate Dip Switches
ON
BAUD Rate
B1
B2
B3
B4
9600
OFF
OFF
OFF
OFF
1200
ON
OFF
OFF
OFF
2400
ON
ON
OFF
OFF
4800
ON
OFF
ON
OFF
9600
ON
ON
ON
OFF
19200
ON
OFF
OFF
ON
38400
ON
ON
OFF
ON
57600
ON
OFF
ON
ON
115200
ON
ON
ON
ON