beautypg.com

ONICON System-30 MODBUS BTU User Manual

Page 26

background image

11451 South Belcher Road, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-30 BTU Measurement System MODBUS RTU RS485 04/14 - 0583-1 / 18345

Page 26

4.5 BAUD RATE

Every ONICON Btu meter is individually programmed at the factory with application specific

data provided by the customer during the process of ordering the meter. This normally

includes the Baud rate setting. If the Baud rate was provided, the Btu meter will be configured to

operate at the specified rate. The available Baud rate settings are listed in the table below.


If the Baud rate setting was not provided to ONICON, the Btu meter will be configured to 9600.


The Baud rate setting can be manually changed in the field. The drawing and table below show

the Baud rate dipswitch settings.

Baud Rate Dip Switches

ON

BAUD Rate

B1

B2

B3

B4

9600

OFF

OFF

OFF

OFF

1200

ON

OFF

OFF

OFF

2400

ON

ON

OFF

OFF

4800

ON

OFF

ON

OFF

9600

ON

ON

ON

OFF

19200

ON

OFF

OFF

ON

38400

ON

ON

OFF

ON

57600

ON

OFF

ON

ON

115200

ON

ON

ON

ON

This manual is related to the following products: