Register
Address

Description

Register

Range

Data

Range

Over

Range

Read/Write

Comment

40001

Meter Operating Mode
Indicator

1 – 3

Not

applicable

Read Only

1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode

40002

Mode Status Indicator

1 – 2

Not

applicable

Read Only

1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction

40003

Energy Rate – Btu/Hr

0 – 65535

0 - 65534

65535

Read Only

40004

Energy Rate – kBtu/Hr

0 – 65535

0 - 65534

65535

Read Only

40005

Energy Rate – MBtu/Hr

0 – 65535

0 - 65534

65535

Read Only

40006

Energy Rate – kW

0 – 65535

0 - 65534

65535

Read Only

40007

Energy Rate – kW x 10

0 – 65535

0 - 65534

65535

Read Only

40008

Energy Rate – Tons

0 – 65535

0 - 65534

65535

Read Only

40009

Volume Rate – GPM

0 – 65535

0 – 65534

65535

Read Only

40010

Volume Rate – GPM x 10

0 – 65535

0 – 65534

65535

Read Only

40011

Volume Rate – GPH

0 – 65535

0 – 65534

65535

Read Only

40012

Volume Rate – MGD

0 – 65535

0 – 65534

65535

Read Only

40013

Volume Rate – L/S

0 – 65535

0 – 65534

65535

Read Only

40014

Volume Rate – L/M

0 – 65535

0 – 65534

65535

Read Only

40015

Volume Rate – L/Hr

0 – 65535

0 – 65534

65535

Read Only

40016

Volume Rate – M³/Hr

0 – 65535

0 – 65534

65535

Read Only

40017

Volume Rate – M³/Hr x 10

0 – 65535

0 – 65534

65535

Read Only

40018

Mass Rate – Lb/Hr

0 – 65535

0 – 65534

65535

Read Only

Mass units are only
available when using
F-2000 Vortex Meter.

40019

Mass Rate – Lb/Hr x 10

0 – 65535

0 – 65534

65535

Read Only

40020

Mass Rate – kg/Hr

0 – 65535

0 – 65534

65535

Read Only

40021

Mass Rate – kg/Hr x 10

0 – 65535

0 – 65534

65535

Read Only

40022

Supply Temperature – °F

0 – 65535

0 - 655.35

Not

applicable

Read Only

Multiply by 0.01 to read
temperature to 2 decimal
places.

40023

Return Temperature – °F

0 – 65535

0 - 655.35

Not

applicable

Read Only

40024

Supply Temperature – °C

-32768

to

+32767

-327.68

to

+327.67

Not

applicable

Read Only

40025

Return Temperature – °C

-32768

to

+32767

-327.68

to

+327.67

Not

applicable

Read Only

40026

Energy Total Mode 1 - kBtu

0 – 65535

0 – 999

Read Only

Low Order

40027

Energy Total Mode 1 - MBtu

0 – 65535

0 – 999

Read Only

Middle Order

40028

Energy Total Mode 1

GBtu 0 – 65535

0 – 65534

65535

Read Only

High Order

40029

Energy Total Mode 2 – kBtu

0 – 65535

0 – 999

Read Only

Low Order