System-30 BTU Measurement System MODBUS RTU RS485 04/14 - 0583-1 / 18345

Page 31

Register
Address

Description

Register

Range

Data

Range

Over

Range

Read/Write

Comment

40030

Energy Total Mode 2 – MBtu

0 – 65535

0 – 999

Read Only

Middle Order

40031

Energy Total Mode 2 – GBtu

0 – 65535

0 – 65534

65535

Read Only

High Order

40032

Energy Total Mode 1 – TonHr

0 – 65535

0 – 999

Read Only

Low Order

40033

Energy Total Mode 1 – kTonHr

0 – 65535

0 – 65534

65535

Read Only

High Order

40034

Energy Total Mode 2 – TonHr

0 – 65535

0 – 999

Read Only

Low Order

40035

Energy Total Mode 2 – kTonHr

0 – 65535

0 – 65534

65535

Read Only

High Order

40036

Energy Total Mode 1 – kWHr

0 – 65535

0 – 999

Read Only

Low Order

40037

Energy Total Mode 1 – MWHr

0 – 65535

0 – 999

Read Only

Middle Order

40038

Energy Total Mode 1 – GWHr

0 – 65535

0 – 65534

65535

Read Only

High Order

40039

Energy Total Mode 2 – kWHr

0 – 65535

0 – 999

Read Only

Low Order

40040

Energy Total Mode 2 – MWHr

0 – 65535

0 – 999

Read Only

Middle Order

40041

Energy Total Mode 2 – GWHr

0 – 65535

0 – 65534

65535

Read Only

High Order

40042

Volume Total Mode 1 - kGal

0 – 65535

0 – 999

Read Only

Low Order

40043

Volume Total Mode 1 - MGal

0 – 65535

0 – 999

Read Only

Middle Order

40044

Volume Total Mode 1 – GGal

0 – 65535

0 – 65534

65535

Read Only

High Order

40045

Volume Total Mode 2 – kGal

0 – 65535

0 – 999

Read Only

Low Order

40046

Volume Total Mode 2 – MGal

0 – 65535

0 – 999

Read Only

Middle Order

40047

Volume Total Mode 2 – GGal

0 – 65535

0 – 65534

65535

Read Only

High Order

40048

Volume Total Mode 1 – kLiters

0 – 65535

0 – 999

Read Only

Low Order

40049

Volume Total Mode 1

MLiters

0 – 65535

0 – 999

Read Only

Middle Order

40050

Volume Total Mode 1 – GLiters

0 – 65535

0 – 65534

65535

Read Only

High Order

40051

Volume Total Mode 2 – kLiters

0 – 65535

0 – 999

Read Only

Low Order

40052

Volume Total Mode 2

MLiters

0 – 65535

0 – 999

Read Only

Middle Order

40053

Volume Total Mode 2 – GLiters

0 – 65535

0 – 65534

65535

Read Only

High Order

40054

Volume Total Mode 1 –M³

0 – 65535

0 – 999

Read Only

Low Order

40055

Volume Total Mode 1 – kM³

0 – 65535

0 – 65534

65535

Read Only

High Order

40056

Volume Total Mode 2 –M³

0 – 65535

0 – 999

Read Only

Low Order

40057

Volume Total Mode 2 – kM³

0 – 65535

0 – 65534

65535

Read Only

High Order

40058

Mass Total – kLbs

0 – 65535

0 – 999

Read Only

Mass units are only
available when using
F-2000 Vortex Meter.

40059

Mass Total – MLbs

0 – 65535

0 – 65534

65535

Read Only

40060

Mass Total – Kkgs

0 – 65535

0 – 999

Read Only

40061

Mass Total – Mkgs

0 – 65535

0 – 65534

65535

Read Only

40062

Auxiliary Input Total

0 – 65535

0 – 999

Read Only

Low Order

40063

Auxiliary Input Total (x1000)

0 – 65535

0 – 65534

65535

Read Only

High Order

40064

Zero Mode 1 Energy Total

0 – 1

0 – 1

Not

applicable

Read/Write

Write a value of 1 to
registers to reset totals.
Re-write a value of zero
to registers once the
totals reset.

40065

Zero Mode 1 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

40066

Zero Mode 2 Energy Total

0 – 1

0 – 1

Not

applicable

Read/Write

40067

Zero Mode 2 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

40068

Zero Auxiliary Input Total

0 – 1

0 – 1

Not

applicable

Read/Write