ONICON F-5100 Insertion User Manual
Page 24
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5100 Insertion Thermal Mass Flow Meter Manual 05/15 - 0663-20 / 18333
Page 24
4.4 START-UP & COMMISSIONING
Please read the entire procedure before proceeding. A worksheet for checking off the following
steps and recording measured values is located on the next page.
1.
Confirm flow sensor location.
Confirm adequate straight pipe run
to achieve desired results.
Is the sensor located in the correct location as required by the plans?
Compare the actual straight pipe upstream and downstream of the
sensor location to recommended distances identified in this manual.
If straight pipe run is very short, consult ONICON PRIOR to
installing the sensor to discuss the possibility of using a flow
conditioner.
2.
Confirm pipe size.
Confirm that the sensor is tagged for the pipe size in which it is
installed. When in doubt, measure the circumference of the pipe.
Pipe O.D. = (circumference / 3.14) – (insulation thickness x 2).
3.
Confirm insertion depth and
orientation.
Refer to the information in section 3.3.1 of this manual to ensure
that the sensor is inserted to the correct depth. Also confirm that the
electronics enclosure is parallel with the pipe and properly oriented
with respect to the direction of flow.
4.
Confirm control system
programming.
Confirm that the control system input point is properly configured
for the analog range and/or scale factor identified on the calibration
tag & certificate.
5.
Confirm connection to correct
ONICON display
Confirm that the flow sensor serial number matches the ONICON
display (when ordered together).
6.
Verify wiring before connecting
power.
Prior to connecting the power, verify that the wiring is correct as
shown in this manual and/or on additional wiring diagrams
provided with the ONICON display. If in doubt, contact ONICON for
assistance before proceeding further.
7.
Confirm correct supply voltage.
Verify that the supply voltage matches the voltage listed on the
sensor tag.
8.
Connect power.
Wait approximately 45 seconds after power-on before proceeding
further.
The following steps require flow in the pipe. Flow signal readings should be taken while holding the flow rate
constant, if possible. Otherwise, take the various output readings as quickly as possible.
9.
Measure and record analog and
pulse outputs.
Current Output:
Scaled Output:
Refer to flow sensor wiring diagram to locate the correct output
terminals. Use the following formula to calculate the flow rate from
the analog signal measurement:
SCFM = (measured current in mA - 4) X Full Scale Flow Rate
16
Each 24VDC pulse = unit volume identified as “Scale Factor”
(measure and record time interval between pulses)
10. Compare output signals to each
other and to the flow rate displayed
by the control system.
Compare the flow rate calculated in step 9 to the flow rate indicated
by the control system. Confirm that the control system is registering
scaled output pulses as they occur.
Refer to troubleshooting guide when readings are inconsistent.