ONICON F-5100 Insertion User Manual
Page 17
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5100 Insertion Thermal Mass Flow Meter Manual 05/15 - 0663-20 / 18333
Page 17
Tightening the Compression Fitting
1.
Insert the sensor as described above.
2.
Tighten the nut until the stem will not turn by hand or
move axially in the fitting.
3.
Mark the nut at the 6 o’clock position.
4.
While holding the fitting body steady, tighten the nut one
and one quarter (1¼) turns to the 9 o’clock position.
CAUTION
The compression fitting must be tightened as described in the following procedure. Failure to do
will likely result in fluid leaks and/or permanent damage to the flow sensor stem.
!
Collar
Collar
For high pressure kits, position upper collar as shown and
then tighten both collars to complete the installation.