Olson Technology MUSCLE-EM55X User Manual
Page 40
OTOT-EM55X/XL Optical Transmitter Rev. x1
www.olsontech.com
39
• Let´s guess, that I/O #0 is set to output on any warning (and alarm)
• Let´s guess, that I/O #1 is set to output on any alarm (no warnings)
Now let’s assume some alarm situations:
1. RF input of OTOT-EM55X is low (warning); Optical Amplifier has no warnings or alarms
The I /Os will be:
Output #0: active
Output #1: inactive
2. RF input level of OTOT-EM55XL is extremely low (alarm)
The I/Os will be:
Output #0: active
Output #1: active
3. Optical input power level of Optical Amplifier is low (warning); OTOT-EM55X has no warnings or alarms:
The I/Os will be:
Output #0: inactive
Output #1: inactive
4. Optical input power level of Optical Amplifier is low (warning); OTOT-EM55X has no warnings or alarms:
The I /Os will be:
Output #0: inactive
Output #1: inactive
5. Optical input power level of Optical Amplifier is low (warning); OTOT-EM55X has no warnings or alarms; I/O #2
is set to alarm on input;I/O #2 receives an alarm
The I /Os will be:
Output #0: inactive
Output #1: active
6. Optical input power level of Optical Amplifier is very low (alarm); OTOT-EM55X has no warnings or alarms:
The I /Os will be:
Output #0: inactive
Output #1: active