Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
7
CR#
HW
LW
Attribute
Content
Explanation
#7
R
Status of E-Mail 1, 2
b0 ~ b7: Current status of E-Mail 2
b8 ~ b15: Current status of E-Mail 1
#8
R
Status of E-Mail 3, 4
b0 ~ b7: Current status of E-Mail 4
b8 ~ b15: Current status of E-Mail 3
#9 R/W
E-Mail 1 additional
message
Filled in by the user, and it will be send by E-mail.
#10 R/W
E-Mail 2 additional
message
Filled in by the user, and it will be send by E-mail.
#11 R/W
E-Mail 3 additional
message
Filled in by the user, and it will be send by E-mail.
#12 R/W
E-Mail 4 additional
message
Filled in by the user, and it will be send by E-mail.
#13
R/W
Data exchange trigger
Set up whether to send out data in data exchange mode
#14
R
Status of data exchange Displaying current status of data exchange.
#15 RW
Enabling flag for RTU
mapping
1: Enable; 0: Disable. Default = 0
#16 RW
Connection status of
RTU mapping slave
b0: Status of RTU slave 1
b1: Status of RTU slave 2
b2: Status of RTU slave 3
b3: Status of RTU slave 4
#24 ~ #17
-
Reserved
#26 #25 R/W Destination
IP
Destination IP address for data exchange
#27 - Reserved
#28
R/W
Destination Slave ID
Destination Slave ID for data exchange
#48 ~ #29
R/W
Data transmission buffer Buffer for transmitted data in data exchange
#68 ~ #49
R
Data receiving buffer
Buffer for received data in data exchange
#80 ~ #69
-
Reserved
#81 R/W
Read address for data
exchange
Slave transmission buffer address for data exchange
#82 R/W
Read length for data
exchange
Number of registers for read data
#83 R/W
Received address for
data exchange
Buffer address for the receiving Master in data exchange
#84 R/W
Written-in address for
data exchange
Buffer address for the receiving Slave in data exchange
#85 R/W
Written-in length for data
exchange
Number of registers for data transmission
#86 R/W
Transmission address
for data exchange
Master transmission buffer address for data exchange
#110 ~ #87
-
Reserved
#111
R/W
8-bit processing mode
Setting up Modbus TCP Master control as 8-bit mode
#112
R/W
Modbus TCP Keep-Alive
Time-out
Modbus TCP Keep-Alive Time-out (s)
#113
-
Reserved
#114
R/W
Modbus TCP time-out
Setting up Modbus TCP time-out (in ms)