Ethernet communication module dvpen01-sl – Delta DVPEN01-SL User Manual

Page 13

background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

11

C R # 8 3 :

Read Length for Data Exchange

Explanations:

Setting up the Modbus address of the register for Master data exchange.

C R # 8 4 :

Written-in Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange.

C R # 8 5 :

Written-in Address for Data Exchange

Explanations:

The number of transmission registers (K1 ~ K100) in data exchange.

C R # 8 6 :

Transmission Address for Data Exchange

Explanations:

1. Setting up the Modbus address of the register for Master data exchange.

2. Example: Write H’1000 (D0) into CR#81, K1 into CR#82, and H’1064 (D100) into CR#83. If

the data exchange is successful, the value in D0 of the Slave will be written into D100 of the

MPU. Or write H’1002 (D2) into CR#84, K4 into CR#85, and H’1008 (D8) into CR#86. If the

data exchange is successful, the value in D8 ~ D11 of the Master will be written into D2 ~ D5

of the Slave. Both sending and receiving can be executed at the same time. When the values

in CR#82 and #85 are both “0”, DVPEN01-SL will use the default registers (CR#29 ~ CR#68)

and number of registers (K20).

„

Sending Modbus TCP Instruction

C R # 111 :

8-bit Processing Mode

Explanations:

Setting up the Modbus TCP transmission mode. When the CR value is set as “0” Æ 16-bit mode;

when the CR value is set as “1” Æ 8-bit mode.

C R # 11 2 :

Modbus Client Keep-Alive Time-out

Explanations:

CR#112 is the TCP Keep-Alive time-out for Modbus TCP connection (s). Default: 30s. If the

connection idle time becomes longer than the keep-alive time-out, DVPEN01-SL will cut off the

idle connection.