Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

25

E-Mail will be sent to the designated recipients when the E-Mail is triggered. To trigger E-Mail, set

the value is CR#3 ~ CR#6 as “1”.

6. See “Application Examples Section 6.8” for more details.

Notes:

To correctly send out E-Mails, there has to be a SMTP server in the network. When we send out

an E-Mail, the mail will be sent to SMTP server first, and the server will further send the mail to the

designated address.

5.5 Data

Exchange

DVPEN01-SL is able to designate a data exchange area for PLC MPUs to exchange and synchronize their

data.

„

Setting up DVPEN01-SL data exchange

1.

Enable

Data

Exchange:

Check the box to enable or disable data exchange. Start data exchange after enable it.

2. Execute Mode:

You can set it to ”Always Enable” or ”Program Control”. When set to “Always Enable”,

DVPEN01-SL will execute data exchange continuously until the setting in DCISoft is changed.

When set to “Program Control”, DVPEN01-SL will execute data exchange according to the

program setting (CR#13 = 2: Execute; CR#13 = 0: Stop).

3. Communication Address & Data exchange host IP:

You have to enter the IP address of DVPEN01-SL at the other end. For example, if you would

like DVPEN01-SL to exchange data with 192.168.0.1, set No. 1 as 192.168.0.1. When the data

are being exchanged, if the value in CR#28 is H’0001, the data will be exchanged with

192.168.0.1.

4. Master Address & Slave address & Quantity.

Read (Å): Start address of the master’s receiving register Å Start address of the slave’s

sending register

Write (Æ): Start address of the master’s sending register Æ Start address of the slave’s