3 product designation / which model do you have, 4 ul approved installation, Product designation / which model do you have – Nortec ME Control Installation User Manual
Page 9: Ul approved installation
9
Important notes on installation
3.3
Product designation / Which model do you have
The product designation and the most important unit data are found on the rating plate fixed to the
evaporative module and the control unit.
Information regarding the rating plate and the product key can be found in the operation manual of the
Nortec ME Control.
3.4
UL approved installation
In order to maintain a UL approved installation, the following installation requirements must be met,
otherwise the Nortec ME system will not be approved under UL998.
1. The Nortec ME Control hydraulic unit must be installed external to the air stream in accordance with
the typical installation drawing in chapter 4.1.2 – Typical installation Nortec ME Control (external
2. All interconnecting piping and connections between the evaporative module and the hydraulic unit,
in direct contact with the air stream must be either copper or stainless steel.
Note: water quality should be considered when selecting an appropriate material (i.e. copper is not
suitable for RO water).
3. The Nortec ME Control unit contains a large reservoir of water when in operation. Install the ME unit
where is no risk of water damage, otherwise make provisions to contain any leakage.