2 water installation (internal installation), Water installation (internal installation) – Nortec ME Control Installation User Manual
Page 28

28 Installation
–
Notes on water supply
–	 The	water	supply	is	to	be	carried	out	according	to	the	figures	found	in	chapter	4.4.4 – Mount-
ing the control unit and 4.4.3 – Water installation (external installation) and the applicable local
regulations for water installations. The indicated connection specifications must be observed.
The installation material must be supplied by the customer.
– The installation of a
shut-off valve in the supply line is mandatory and should be made as close
as possible to the hydraulic module.
–	 Regarding	supply	water	quality	see	appendix.
–	 The	installation	material	must	be	pressure-proof	and	certified	for	use	in	drinking	water	supply	
systems.
– The wall feed through for the water supply must be done by the customer.
Important: after installation the water supply pipe has to be sealed around the feed through
using silicone-free sealant.
–
Important! To prevent new systems being contaminated with low quality water the entire
water supply line must be flushed and tested until the supply water and the bacteria counts,
are in line with the water quality specifications, before connecting it to the hydraulic
module. For water quality requirements refer to chapter 5.1 – Inlet water quality requirements.
–
Notes on water drain
–	 The	water	drain	is	to	be	carried	out	according	to	the	figures	found	in	chapter	4.4.4 – Mounting 
the control unit and 4.4.3 – Water installation (external installation) and the applicable local
regulations for water installations. The indicated connection specifications must be observed.
The installation material must be supplied by the customer.
–	 Make	sure	the	drain	line	is	installed	with	a	constant	down-slope	down	to	the	tundish.
–	 The	drain	pipe	must	not	touch	the	tundish,	allow	air	gap	of	min	20	mm	(0.8").
–	 Make	sure	the	drain	pipe,	the	drain	trap	and	the	tundish	are	correctly	fixed	and	easily	accessible	
for inspections and cleaning purposes.
– Access hole for the drain pipe through the duct/AHU must be provided by the customer.
Important: after installation the drain pipe has to be sealed around the feed throughs us-
ing silicone-free sealant.
–	 The	minimum	inside	diameter	of	the	drain	pipe	must	be	maintained	throughout	the	entire	length!
–	 The	drain	pipe	must	be	vented	to	the	interior	of	the	duct	in	accordance	with	the	figures	found	in	
chapter 4.4.4 – Mounting the control unit and 4.4.3 – Water installation (external installation).
–
Notes on pressure equalisation for external mounted systems
–	 The	hydraulic	module	must	be	equipped	with	a	pressure	equalisation	pipe	connected	to	the	
interior of the duct to ensure the level in the hydraulic module corresponds with the level in the
tank inside the duct (see figure in chapter 4.4.3 – Water installation (external installation).