beautypg.com

Maintenance/service, Troubleshooting – Nortec Blower Packs User Manual

Page 25

background image

Blower Pack Installation Guide | 22

Maintenance/Service

The RM-BP and NH-EL Humidifier have been designed to require very little maintenance. Regular
maintenance consists of checking the humidifier to insure it is in good condition, cleaning out the
intake grill of dust and inspecting wiring on inside of blower pack.

Performance of the Fan may become reduced temporarily if significant dust build-up occurs on both
RM-BP and NH-EL Space models. It is recommended to take a vacuum or similar to remove all dust
build up on the top of the humidifier as accumulation occurs throughout the span of a year.

Troubleshooting

Symptom

Cause

Corrective Action(s)

Blower not operating

Note: Blower pack does not turn on unless

steam is being produced by the humidifier.

1 No power to blower pack

1a Check power connection.
1b Check NH-EL fusing and

Transformer

Steam coming out but blower pack not

running

1 On/Off Thermostat not closing

2a Ensure Steam supplied to Blower

Pack

2b Verify Wire continuity to

temperature switch.

2 Very High Ambient

temperature

NH-EL Humidifier not running
with Blower Pack Warning:
security loop Open

1 Security loop wiring missing

between Blower Pack and
NHEL low voltage terminal
strip

2 No power to blower pack

1 Wire blower pack security loop

to blower pack


2 Check power connection