beautypg.com

Nortec Blower Packs User Manual

Page 17

background image

Blower Pack Installation Guide | 14

Trap Condensate

Trap at all low points and recommended intervals using full size ‘T’ for traps.

Condensate should not be routed to a sink used frequently by personnel. Route to a floor

drain or equivalent. Condensate normally cools in traps but is still hot. A larger steam line

generates more condensate and water may not cool in the trap. A drain water cooler

option may be installed if required by code.

Route condensate to floor drain or equivalent in multi-unit to single RM-BP.

Do not install electric zone valves on steam lines. Improper adjustment will over-pressurize

the humidifier.

Steam Line Rules
The following 10 points provide rules for installing steam lines connecting

the NH–EL humidifier to RM-BP. In addition to these rules never use

unapproved material for steam lines.

Figure 11. condensate Plumbing