Operation
Putting into Operation
Proceed as follows when putting the Nortec MH into operation:
•
Examine the Nortec MH and installation for possible damage.
Damaged devices or devices with damaged installation may present danger to human life or
cause severe damage to material assets.
Damaged units and/or units with damaged or faulty installation must not be operated.
•
Models MHB Flow, MHTC Flow, MHB Reflow, MHTC Reflow: Make sure the connecting
box(es) and the control unit are closed and that all cables are lead through cable glands.
•
Open the shut-off valve in the water supply line.
•
Switch on the service switch in the mains supply.
•
Models MHTC Flow, MHB Reflow, MHTC Reflow: Switch on the MH Control Unit (the unit
switch lights up).
•
For operation of the NORTEC MH Series Control Unit, please refer to the information
provided in the separate operating instructions for the NORTEC MH Control Unit.
•
Check the settings of the humidistat/thermostat or the humidity controller, respectively. If
necessary, adjust settings.