INSTALLATION (cont.)

LCDI Power Cord Instruction

WARNING: This LCDI power cord is a non-serviceable device.

Attempting to open the device may expose the user to the hazards

of electric shock, and could void warranties of this product.

Manufacture’s reliability is limited to the replacement of the device.
CAUTION:

• Read the attention printed on the device for proper use and handling

of this device.

• This device is used for monitoring leakage current.

• Do not immerse in water.

• This device must only be plugged into an appropriate wall outlet. Do

not remove the ground prong.

• In the event that this device trips, the cause of malfunctions should

be corrected first before further use.

• Using the device beyond the recommended voltage poses risk to

users.

• Conductors inside this cord are surrounded by shields, which

monitor leakage current.

• These shields are not grounded, and they are periodically examined

for any damage.

Do not use this product in the event the shields become exposed.

• Do not repleatedly push TEST and/or RESET buttons.

Test Procedure

Test this device once when the power supply is installed to assure proper

operation.

1. Plug into the grounded power receptacle.

2. If POWER light is not on, press RESET button once. Light should turn on.

3. Press TEST button once, POWER light must turn off.

4. Press RESET button once again for use. POWER light should turn on.

5. If this test fails, do not use this device. Contact a qualified technician for

details.

Reset Button

Test Button

ILL00049-01