OPERATION (cont.)

Operating Modes

The Classic 40 and Classic 60 can be operated in two modes, FAN ONLY and

COOL. When in FAN ONLY mode, the unit circulates the surrounding air. When in

COOL mode, the compressor is operated and cool air is circulated.
1. COOL Mode

Once the compressor has been disengaged for more than 120 sec, the unit

operates in FAN ONLY mode for approximately 5 sec before the compressor

re-engages.

2. Temperature Control

The room temperature thermistor monitors the inlet temperature versus set

point temperature and switches the unit automatically between COOL and

FAN ONLY modes.

3. Fan Mode Control DIP Switch

The fan mode control DIP switch determines whether the fan continues to

operate or stop when the compressor cycles off. (Set point temperature below

the inlet air or room temperature.) The unit has been preset at the factory for

continuous fan operation.
Note: If you want to change the fan mode operation (from OPERATE to

STOP), contact your MovinCool reseller.

4. Temperature Scale Display

The temperature scale display changes the temperature(s) that are displayed

to either °C or °F. The unit has been preset from the factory to display the

temperature(s) in °F.
Note: If you want to change the temperature scale display (from °F to °C), hold
down the SET TEMP buttons (

/

) and the FAN button simultaneously for

3 sec.