INSTALLATION (cont.)

Warning Signal Connection

(Output Signal Terminal L+ and L-) (cont.)

Connecting Warning Signal from Controller

3. Insert the warning signal wire through the clip, grommet, and hole in the right

side panel.

Note: Use recommended warning signal wire size from 16 AWG to 26 AWG

for a solid wire, or 16 AWG to 22 AWG for a stranded wire with ring terminal

for #6 stud size.

4. Connect the warning device to terminal L+ and L- according to its polarities.

UNIT TERMINAL

INPUT SIGNAL

RELAY OUTPUT CONTACTOR

WARNING DEVICE

E+
E-

L+
L-