Installation (cont.) – MovinCool Classic 40 User Manual
Page 14

14
INSTALLATION (cont.)
Power Supply and Field Wiring Connection (For Classic
60 ONLY)
Power Supply
• AC 460 V±10 %, 3 phase and 60 Hz. Do not connect the unit to any other power
supply.
• The power supply should be a dedicated single outlet circuit with a UL approved
short-circuit and ground fault protective breaker with a recommended fuse size
of 20 A (20 A maximum).
• Securely tighten each terminal.
CAUTION:
Use a specified 20 A fuse. Do not use wiring, copper wire or
soldering instead of the fuse. The use of non-specified fuses can cause
machine failure or fire.
CIRCUIT BREAKER WITH
GROUND-FAULT PROTECTIVE
FUSE 20 A (20 A MAX.)
R
S
T
G
R
S
T
G
TERMINAL BLOCK OF Classic 60
GROUNDING
TERMINAL
GREEN
COLORED WIRE
POWER SOURCE
AC 460 V, 3 PHASE, 60 Hz