INSTALLATION (cont.)

Optional Accessories and Set Up Configuration (cont.)

Unit Suspended from the Ceiling (For Classic 40 ONLY)

When the unit is suspended from the ceiling, cooling air can be sent from the

bottom of the unit. More information is available at WWW.MOVINCOOL.COM.

WARNING:

Make sure that the ceiling structure is capable of

supporting the weigh of the unit, suspension hardware, and the

accessories.

Note:
1. Use standard suspension metal fittings.
2. Do not suspend the unit from the ceiling of a lightweight steel-frame building or

wooden building.

3. Make sure to lock the shackle pin with copper wire.
4. Make sure to securely tighten the nut-tightening portion with double-nut locking.
5. If you are uncertain about the strength of ceiling structure, from which the unit

is suspended, consult the architect.

6. When working in high places during the installation of unit, provide positive

safeguards, such as using a lifeline.

7. After the unit is suspended from the ceiling, make sure that the unit is level. If

the unit is not level, adjust each suspension length of the unit with an eyebolt.

If the unit slans more than 1.5° horizontally, the drain water will overflow.

8. When the unit is configured as suspended from the ceiling, the signal output can

be used with alarm speaker or light indicator to monitor proper operation.

U-BOLT

EYE BOLT

EYE NUT

SECURELY TIGHTEN WITH

DOUBLE NUT LOCKING

LOCK BY BINDING WITH

1/16 in. DIA. COPPER WIRE

SHACKLE

BRACKET

SPAN OF BUILDING

DUCT

SHACKLE

SHACKLE

SHACKLE PIN

ROD

ROD