background image

USB-1096HFS User's Guide

Installing the USB-1096HFS

Unpacking the USB-1096HFS

As with any electronic device, you should take care while handling to avoid damage from static
electricity. Before removing the USB-1096HFS from its packaging, ground yourself using a wrist strap or by
simply touching the computer chassis or other grounded object to eliminate any stored static charge.

If any components are missing or damaged, notify Measurement Computing Corporation immediately by
phone, fax, or e-mail:

!

Phone: 508-946-5100 and follow the instructions for reaching Tech Support.

!

Fax: 508-946-9500 to the attention of Tech Support

!

Email:

[email protected]

Installing the software

Refer to the Quick Start Guide for instructions on installing the software on the Measurement Computing Data
Acquisition Software CD
. This booklet is available in PDF at

www.mccdaq.com/PDFmanuals/DAQ-Software-

Quick-Start.pdf

.

Installing the hardware

Before you connect the USB-1096HFS to your computer, connect the external power supply that was shipped
with the device.

You can connect up to four MCC USB Series products in a daisy chain configuration to a single USB 1.1 port
or USB 2.0 port on your computer.

Connecting the external power supply

Power to the USB-1096HFS is provided with the +9 V external power supply (CB-PWR-9V3A). You must
connect the external power supply before connecting the USB cable to the USB-1096HFS and your computer.

If you are connecting more than one board, make sure that you provide adequate power to each device. Refer to
the

Power limitations using multiple USB-1096HFS devices

section on page 3-6.

To connect the power supply to your USB-1096HFS, connect the external power cord to the power connector
labeled

POWER IN

on the USB-1096HFS enclosure (

J3

on the board). Refer to

on page 3-1 for the

location of this connector.

Figure 3-1

The

PWR

LED illuminates green when +9 V power is supplied to the USB-1096HFS. If the voltage supply is

less than +6.0 V or more than +12.5 V, the

PWR

LED does not light.

Do not connect external power to the POWER OUT connector
The power connector labeled

POWER OUT

on the enclosure (

J4

on the board) is used to provide power to an

additional MCC USB Series product. If you connect the external power supply to the

POWER OUT

connector,

the USB-1096HFS does not receive power, and the

PWR

LED does not illuminate.

Connecting the USB-1096HFS to your system

To connect the USB-1096HFS to your system, connect the USB cable to a USB port on your computer or to an
external USB hub that is connected to your computer. The USB cable provides communication to the USB-
1096HFS.

When you connect the USB-1096HFS for the first time, multiple

Found New Hardware

popup balloons

(Windows XP) or dialogs (other Windows versions) appear as the USB-1096HFS is detected.