beautypg.com

Ch 5 - discrete output modules, 8 channel output modules, Standard base – Measurement Computing PointScan 300 Series rev.1.0 User Manual

Page 23: Optional) universal wiring base, Output isolation, Watchdog output feature, 5 - discrete output modules, 8 channel output modules -1, Discrete output modules 5

background image

PointScan/300 User’s Manual

9-12-01

Discrete Output Modules 5-1

Discrete Output Modules

5

This section documents the following modules:

PointScan/336

PointScan/337

PointScan/339

PointScan/340

PointScan/341

8 Channel Output Modules

PointScan/300 Series eight channel discrete output modules incorporate one of two module base styles.
These base styles and other features are detailed below.

Standard Base

With the standard base, one terminal from each channel is connected to an internal common bus. A single
user power connection to the module allows up to eight output devices to be connected in sourcing or
sinking configurations using two wires apiece. This is the most common wiring configuration. Refer to the
next page for sample wiring connections.

(Optional) Universal Wiring Base (-w)

With the (optional) Universal Wiring base, each discrete output has two independent screw terminals to
provide point to point isolation. Sample wiring is shown on the next page.

Output Isolation

All discrete outputs are optically isolated from the PointScan/300 Series circuitry, regardless of the module
base style. If the (optional) Universal base is used, the discrete outputs will be channel to channel isolated
as well.

Watchdog Output Feature

The first DC output channel may be configured (in software) as a watchdog output. If this feature is
selected, the output will be on when there is good command activity from the gateway. The output will no
longer be controlled as a discrete output. The corresponding register will be unused.