3-2 Power and PT-Bus Wiring

9-12-01

PointScan/300 User’s Manual

PT-Bus Wiring Guidelines

PT-Bus wiring connects the PointScan/300 Series I/O modules and expanders to the gateway. Follow the
guidelines for reliable performance.

PT-Bus Capability

Max. modules controlled by one gateway

128

Max. modules connected directly to gateway

20 (any mix)

Required cable type

Any with 2 individually
shielded pairs, 22AWG min.

Recommended cables

Alpha 2466C, Belden 8723,
Carol C1352

Max. cabling off each gateway or expander

50 ft. (16M)

Connect up to 20 I/O modules directly to the
gateway with a maximum total cabling of 50 feet
(16m).

PT-Bus connections may form star configurations
without restrictions.

PT-Bus wiring may be extended into additional cabinets as long as the total length of wire
connected to the gateway or expander stays within the 50 foot limit (16m).

Use the supplied PT-Bus jumpers between adjacent PointScan components. Otherwise, use the
recommended cable.