Unpacking the usb-ssr08, Installing the software, Installing the usb-ssr08 – Measurement Computing USB-SSR08 User Manual
Page 11: Configuring the hardware switches, Unpacking the usb-ssr08 -2, Installing the software -2, Installing the usb-ssr08 -2, Configuring the hardware switches -2

USB-SSR08 User's Guide
Installing the USB-SSR08
Unpacking the USB-SSR08
As with any electronic device, you should take care while handling to avoid damage from static
electricity. Before removing the USB-SSR08 from its packaging, ground yourself using a wrist strap or by
simply touching the computer chassis or other grounded object to eliminate any stored static charge.
If your USB-SSR08 is damaged, notify Measurement Computing Corporation immediately by phone, fax, or
email. For international customers, contact your local distributor where you purchased the USB-SSR08.
Phone: 508-946-5100 and follow the instructions for reaching Tech Support.
Fax: 508-946-9500 to the attention of Tech Support
Email:
Installing the software
Refer to the Quick Start Guide for instructions on installing the software on the Measurement Computing Data
Acquisition Software CD. This booklet is available in PDF
Installing the USB-SSR08
Before you connect the USB-SSR08 to your computer, configure the hardware and then connect the external
power supply that was shipped with the device. You can connect up to four MCC USB Series products in a
daisy chain configuration to a single USB 1.1 port or USB 2.0 port on your computer.
Configuring the hardware switches
The USB-SSR08 has three on-board switches that you set to configure the I/O module type, relay logic polarity,
and relay power-up state. Configure these switches before you connect the external power supply to the USB-
SSR08. Factory-configured default settings are listed in
switch.
Table 2-1. Default switch configuration
Board label
Description
Default setting
IN OUT (S1)
Configures the I/O type per module group for
input or output.
OUT (output)
NON INVERT INVERT (S2)
Configures the relay logic parity per module
group for invert or non-invert logic.
NON INVERT
(active low)
P/UP P/DN (S3)
Configures the power-up state of output
relays for pull-up or pull-down.
P/UP (Pull-up)
Each DIP switch sets the configuration of one module group. The switch labeled
CL
configures modules 1
through 4, and the switch labeled
CH
configures modules 5 through 8.
CH
CL
No function
No function
Configures modules 5-8
Configures modules 1-4
Figure 2-1. Typical board switch
You can use InstaCal to read the current configuration of each switch.
2-2