beautypg.com

Synchronizing multiple units – Measurement Computing USB-3110 User Manual

Page 16

background image

USB-3110 User's Guide

Functional Details

16

Synchronizing multiple units

You can connect the

SYNCLD

terminal pin (pin 49) of two USB-3110 units together in a master/slave

configuration and simultaneously update the DAC outputs of both devices. Do the following.

1. Connect the SYNCLD pin of the master USB-3110 to the SYNCLD pin of the slave USB-3110.

2. Configure the SYNCLD pin on the slave device for input to receive the D/A LOAD signal from the master

device. Use InstaCal to set the direction of the SYNCLD pin.

3. Configure the SYNCLD pin on the master device for output to generate an output pulse on the SYNCLD

pin.

Set the Universal Library

SIMULTANEOUS

option for each device. Refer to the Universal Library User's Guide

for information on how to configure the USB-3110 with the Universal Library.

When the SYNCLD pin on the slave device receives the signal, the analog output channels on each device are
updated simultaneously.

An example of a master/slave configuration is shown here.

Figure 8. Synchronizing the update of multiple units