Infloor TC 204 Heating Controller User Manual
Page 7

Go to Menu 8 CURVE
There are 3 adjustable values in this menu.
Curve Design
When you use a room sensor the reset curve is self adjusting. You need this section only if you donʼt use a room
sensor and the default curve does not work for your region.
- 10C1
32º F - 248º F
Default 140º F
Supply water temperature at 14º F (- 10º C) outside temperature
+10C1
32º F - 248º F
Default 86º F
Supply water temperature at 50º F (+10º C) outside temperature
The sample reset schedule shown in the chart is the default. To set +10C1 (50º F) & -10C1 (14º F) select the
water temperature you want at those outside temperature on the vertical F scale.
Suggested Initial Settings
Leave +10C1 at 86º. At 50ºF outside the supply temperature will be 86º F.
Set -10C1 so that at the outside design temperature in your area the supply temperature will be near the maxi-
mum temperature allowed in your system.
7
60º F
50º F
40º F
30º F
20º F
10º F
0º F
Outdoor Temperature
100º
120º
140º
160º
180º
200º
-10º F
-20º F
14
S
u
p
p
ly
W
a
te
r
T
e
m
p
e
ra
tu
re
80º
10º C
-10º C
F
190º
170º
150º
130º
110º
90º
70º
Adjustments
Building is always cold
Raise both settings
Building is always warm
Lower both settings
Building gets colder as it gets colder outside
Raise -10C setting
Building gets warmer as it gets colder outside Lower -10C setting
Automatic Curve Adjustment
AUTO
1 or 0 Default 1
When you use a room sensor this should be set at 1. 0 means the curve doesnʼt adapt.
Set it at 0 if there is no room sensor.
Cout1
Calculated Value
All other Menu 8 items are inactive.