Parameter Menu Sub-Menu 1 Sub-Menu 2 Sub-Menu 3

Description

Factory Default

Page 0, Temperature Control

Temperature Control Off

Temperature Control On

ON

Cooling Mode, moving cooling air to space

COOL

Heating Mode, moving heating air to space

Temperature Setpoint in Degrees Fahrenheit, 15°

to 130°, by 1°, Units Controlled by P1

72°F

Temperature Setpoint in Degrees Celsius, -10° to

55°, by 0.5°, Units Controlled by P1

Page 1, Temperature Units

Fahrenheit Degrees

F

Celsius Degrees

Page 2, Humidity Control

Humidity Control Off

OFF

Humidity Control On

Humidity Setpoint, 0 to 100 %RH by 1 %RH

50%

Page 3, Restore Factory Default Menu Values

Entry Screen, Leave Current Values

OFF

Restore Factory Values

Page 4, Display Format

Turn Minor and Major Display Off, Mode Icons On

Show % Fan Speed

Show Space Temperature and Humidity, Depends

on control mode

run

Page 5, Fan Cutout Timer

Fan Cutout Off

OFF

Fan Cutout On

Cutout Timer, 0 to 300 seconds

30

Page 6, Override % Fan Speed

20% to 100% Fan Speed, by 1%

100

Page 7, Manual Fan Speed Override

Manual Fan Speed Override Off

OFF

Manual Fan Speed Override On

Manually Set Fan Speed, 20% to 100% in 1%

increments or 0%

50

Page 8, Minimum % Fan Speed

20

Minimum % Fan Speed Value, 20% to 100% in 1%

increments

Page 9, Maximum % Fan Speed
Maximum % Fan Speed Value, 20% to 100% in

1% increments

100

Page 10, Analog Output Reference

0 to 100 %RH, for 0 to 10 VDC

15° to 130°F or -10° to 55°C, for 0 to 10 VDC,

Units Controlled by P1

t

Parameter P7 continued....
Allows manual control of the fan speed for system

setup and commissioning tests. Exiting this

parameter returns the controller to normal operation.
When entering this parameter, the value shall be

OFF (normal operation). Press the UP button to set

the parameter value to On and then press the ENT

button. The unit is now in manual control.
The major display shall read 50 for 50% output (5

VDC out). The minor display shall show %SPD.
Pressing the UP button shall increase the displayed

value and proportionally change the fan speed.

Pressing the DN button shall decrease the displayed

value and proportionally change the fan speed.
Allowed values are 0% and 20 to 100%, for 0 VDC

and 2 to 10 VDC fan motor control voltage.
The fan speed will remain at the displayed value

until the ENT button is pressed placing the unit back

to the parameter selection mode.
Minimum Fan Speed, Parameter P8
Factory Default = 20%

Parameter P8 continued...
%MIN #
= 20% to 100% in 1% increments
Sets the min fan speed that the controller may

control to. Note: the controller will not allow the

output min to be set higher than the output max.
Maximum Fan Speed, Parameter P9
Factory Default = 100%
%MAX # = 20% to 100% in 1% increments
Sets the max fan speed that the controller may

control to. Note: the controller will not allow the

output max to be set lower than the output min.
Analog Output Reference, Parameter P10
Factory Default = Temperature
REF H = Humidity, 0 to 10V for 0 to 100%RH

REF t = Temperature,

0 to 10V for 15° to 130°F (-10° to 55°C)

An analog output across J15 terminals “REF” and

“GND” for the measured temp or humidity.