Programming (J19 = PRG)

The unit shall ship with factory default parameter

setpoints. Parameter setpoints may be edited in

the field by HVAC technicians. During parameter

editing, the output voltage shall be set to zero.

General Programming

• Enter the edit mode by removing

the unit from its base and

placing jumper J19 on the PRG

pins. The minor display shall

show the parameter name and the major display

shall show the parameter number.

• Press the UP or DN switch to select the

parameter you wish to edit.

• Press the ENT switch to select the parameter and

enter the parameter edit mode. The minor display

shall show the parameter name and the major

display shall show the parameter value.

• Press the UP or DN switch to change the

parameter value. Pressing and holding the

switch will scroll through the values.

• If a parameter has more than one sub-menu (see

tables pgs 6-7), press the ENT switch to reach

the 1st sub-menu and edit the parameter, then

push the ENT switch to reach the 2nd sub-menu

and edit the parameter. Continue until all sub-

menus are edited. Pushing the ENT switch once

more will save and return to the parameter menu.

• Return to normal operation by placing jumper J19

on a single pin.

Parameter Descriptions

Temperature Control, Parameter P0
Factory Defaults = On, COOL, Setpoint 72°F
TMP OFF = Temperature control Off

TMP On = Temperature control On

ACT COOL = Cool Mode, operate fan to lower temp

ACT HEAt = Heat Mode, operate fan to raise temp

SP°F # = Temp Setpoint, 15° to 130°F in 1° increments

SP°C # = Temp Setpoint, -10° to 55°C in 0.5° increments

(°C or °F Temp Setpoint is defined by P1 below)
Temperature Units, Parameter P1
Factory Default = F
DEG F = Fahrenheit degrees

DEG C = Celsius degrees
Humidity Control, Parameter P2
Factory Defaults = OFF, Humidity Setpoint 50%RH
HMD OFF = Humidity control off

HMD On = Humidity control on,

operate fan to decrease humidity

%HSP # = Humidity Setpoint,

0 to 100%RH in 1% increments

Restore Factory Default Parameter

Values, Parameter P3
Factory Default = OFF
FAC OFF = Entry screen, leave current values

FAC On = Restore factory values
Display Format, Parameter P4
Factory Default = run
DIS OFF = Turn minor and major displays off, leave

control mode and fan icons on.

DIS FAn = Unit shows fan speed until scroll button

pushed

DIS run = Unit shows temp or humidity values in

temp or humidity control. Unit toggles

between temp and humidity if both

control modes are enabled.

Fan Cutout Timer, Parameter P5
Factory Default = OFF, 30 seconds
CUT OFF = Cutout timer off

CUT On = Cutout timer on

CTM # = Cutout time, 0 to 300 secs in 1 sec increments
The cutout function turns off the fan when the

temperature and humidity are below their setpoints

for a predetermined amount of time.
Cutout Disabled

The algorithm is run and the FAN output is always

between the min and max speed (Parameters P8 & P9).
Cutout Enabled

When the temp and humidity are below setpoint,

the cutout timer is started and the dot icon on the

display starts flashing. If the timer runs out before

the temp and humidity raises above setpoint, then

the FAN output is set to zero, the dot icon is on

steady and the fan icon is turned off. If the temp and

humidity rises above setpoint (1°F or 3%RH), then

the dot turns off, the fan icon is illuminated and the

FAN resumes algorithm control. The Scroll Button

behaves normally during cutout.
Fan Override, Parameter P6
Factory Default = 100% Fan Speed
%OVR # = Fan Speed of 20 to 100% in 1% increments
During normal operation, when the remote override

switch is closed, the fan will immediately ramp to

P6 speed and stay there until the remote override

switch is opened. The override can be activated by

any normally-open, voltage-free contact. Closing the

contact will activate the override. The fan icon shall turn

on and the display will show %OVR and the %Speed.
Manual Fan Speed Override, Parameter P7
Factory Defaults = OFF, 50% Manual Fan Speed
SPD OFF = Algorithm control

SPD On = Manual control

%SPD # = 20% to 100% in 1% increments, or 0%

J19 Edit Mode